Chapter 5 Operating Instructions
CLV490 Bar Code Scanner
5-4 © SICK AG · Division Auto Ident · Germany · All rights reserved 8009993/RA61/2007-07-20
Electrical installation
b) CLV490 with heater:
The following connection cables with connector cover for the CLV490 can be used:
No. 2033126 (10 m (32.8 ft)) or no. 2033127 (15 m (49.2 ft), however not when the
RS 232 host interface is used)).
The cables must not be extended! If longer cables are required, the entire power supply sys-
tem (Pin 1/Pin 5) must be connected with a wire cross-section of at least 0.75 mm
2
(approx.
20 AWG) with a maximum length of 10 m (32.8 ft).
Note To avoid strain on the power supply lines when connecting the CLV490 with heater to the
CDB420, please make sure to use the correct cable wire diameters for the incoming cables
of the power supply to the CDB420 and to use corresponding fuses. Use only the screw
terminals 1 to 4 for connecting the power supply. The input voltage connected to the screw
terminals 1 and 2 is directly available on the screw terminals 3 and 4 for connecting the
CLV490, independent of the S1 switch (Power).
Chapter 5.3 Connector pin assignment, Page 5-7 shows the pin assignments of the 15-pin
plug and the open cable ends on the side of the CDB420.